41 "38-47-104. Electric vehicle charging facilities - multifamily
42 and large commercial buildings - requirements - definitions. (1) THIS
43 SECTION APPLIES TO THE CONSTRUCTION OF A NEW HIGH-OCCUPANCY
44 BUILDING PROJECT OR TO THE RENOVATION OF FIFTY PERCENT OR MORE
45 OF AN EXISTING HIGH-OCCUPANCY BUILDING PROJECT AND TO:
46 (a) A CONTRACT EXECUTED ON OR AFTER JULY 1, 2023, TO
47 CONSTRUCT A HIGH-OCCUPANCY BUILDING PROJECT;
48 (b) THE PLANNING OF OR DRAFTING FOR A HIGH-OCCUPANCY
49 BUILDING PROJECT ON OR AFTER THE EFFECTIVE DATE OF THIS SECTION;
50 AND
51 (c) THE LAYING OUT OF OR CONSTRUCTION OF A HIGH-OCCUPANCY
52 BUILDING PROJECT ON OR AFTER THE EFFECTIVE DATE OF THIS SECTION.
53 (2) A PERSON THAT IS PLANNING, DESIGNING, OR CONSTRUCTING:
54
1 (a) A LARGE COMMERCIAL BUILDING PROJECT SHALL PLAN,
2 DESIGN, AND CONSTRUCT THE LARGE COMMERCIAL BUILDING PROJECT TO
3 HAVE:
4 (I) TEN PERCENT OF THE PARKING SPACES USED BY THE
5 OCCUPANTS OF THE BUILDING BE EV CAPABLE;
6 (II) TEN PERCENT OF THE PARKING SPACES USED BY THE
7 OCCUPANTS OF THE BUILDING BE EV READY; AND
8 (III) FIVE PERCENT OF THE PARKING SPACES USED BY THE
9 OCCUPANTS OF THE BUILDING TO HAVE EV SUPPLY EQUIPMENT INSTALLED
10 ADJACENT TO A PARKING SPACE; AND
11 (b) A MULTIFAMILY BUILDING SHALL PLAN, DESIGN, AND
12 CONSTRUCT THE MULTIFAMILY BUILDING TO HAVE:
13 (I) IN FIFTY PERCENT OF THE UNITS, A PARKING SPACE USED BY
14 THE OCCUPANTS OF THE BUILDING THAT IS EV CAPABLE;
15 (II) IN TWENTY PERCENT OF THE UNITS, A PARKING SPACE USED BY
16 THE OCCUPANTS OF THE BUILDING THAT IS EV READY; AND
17 (III) IN FIVE PERCENT OF THE UNITS, A PARKING SPACE USED BY
18 THE OCCUPANTS OF THE BUILDING THAT HAS EV SUPPLY EQUIPMENT
19 INSTALLED ADJACENT TO A PARKING SPACE.
20 (3) (a) TO COMPLY WITH THIS SECTION, A PERSON MAY:
21 (I) PARTNER WITH A THIRD-PARTY COMPANY TO INSTALL AND
22 MAINTAIN EV READY PARKING SPACES AND EV SUPPLY EQUIPMENT; OR
23 (II) INCLUDE THE COST OF COMPLYING WITH THIS SECTION IN THE
24 PRICE TO PLAN, DRAFT, OR CONSTRUCT THE HIGH-OCCUPANCY BUILDING
25 PROJECT.
26 (b) A HIGH-OCCUPANCY BUILDING PROJECT OWNER MAY CHARGE
27 THE COST OF COMPLYING WITH THIS SECTION DIRECTLY TO INDIVIDUAL
28 TENANTS THAT USE THE EV READY PARKING SPACES AND EV SUPPLY
29 EQUIPMENT.
30 (c) IN A LARGE COMMERCIAL BUILDING PROJECT THAT IS GROUP A,
31 B, E, I, M, OR S-2 OCCUPANCY, THE NUMBER OF EV SUPPLY EQUIPMENT
32 PARKING SPACES REQUIRED IN SUBSECTION (2)(a) OF THIS SECTION MAY
33 BE REDUCED BY UP TO FIVE IF THE LARGE COMMERCIAL BUILDING PROJECT
34 INSTALLS:
35 (I) A SPACE EQUIPPED WITH LEVEL 3 CHARGING EV SUPPLY
36 EQUIPMENT; AND
37 (II) NOT LESS THAN ONE PARKING SPACE THAT IS EV READY.
38 (4) THIS SECTION DOES NOT PREEMPT A POLITICAL SUBDIVISION OF
39 COLORADO FROM REQUIRING MORE ELECTRIC VEHICLE INFRASTRUCTURE
40 THAN REQUIRED IN THIS SECTION.
41 (5) AS USED IN THIS SECTION:
42 (a) (I) "EV CAPABLE" MEANS A PARKING SPACE THAT:
43 (A) HAS THE ELECTRICAL PANEL CAPACITY AND CONDUIT
44 INSTALLED TO SUPPORT FUTURE IMPLEMENTATION OF ELECTRICAL
45 VEHICLE CHARGING WITH A MINIMUM OF TWO HUNDRED EIGHT VOLTS AND
46 A MINIMUM OF FORTY-AMPERE RATED CIRCUITS; AND
47 (B) IS ADJACENT TO THE TERMINAL POINT OF THE CONDUIT FROM
48 THE ELECTRICAL FACILITIES DESCRIBED IN SUBSECTION (5)(a)(I)(A) OF
49 THIS SECTION.
50 (II) "EV CAPABLE" INCLUDES TWO ADJACENT PARKING SPACES IF
51 THE CONDUIT FOR THE ELECTRICAL FACILITIES DESCRIBED IN SUBSECTION
52 (5)(a)(I)(A) OF THIS SECTION TERMINATES ADJACENT TO AND BETWEEN
53 BOTH PARKING SPACES.
54 (b) (I) "EV READY" MEANS A PARKING SPACE THAT:
55
1 (A) HAS THE ELECTRICAL PANEL CAPACITY, RACEWAY WIRING,
2 RECEPTACLE, AND CIRCUIT OVERPROTECTION DEVICES INSTALLED TO
3 SUPPORT FUTURE IMPLEMENTATION OF ELECTRICAL VEHICLE CHARGING
4 WITH A MINIMUM OF TWO HUNDRED EIGHT VOLTS AND A MINIMUM OF
5 FORTY-AMPERE RATED CIRCUITS; AND
6 (B) IS ADJACENT TO THE RECEPTACLE FOR THE ELECTRICAL
7 FACILITIES DESCRIBED IN SUBSECTION (5)(b)(I)(A) OF THIS SECTION.
8 (II) "EV READY" INCLUDES TWO ADJACENT PARKING SPACES IF
9 THE RECEPTACLE FOR THE ELECTRICAL FACILITIES DESCRIBED IN
10 SUBSECTION (5)(b)(I)(A) OF THIS SECTION IS INSTALLED ADJACENT TO
11 AND BETWEEN BOTH PARKING SPACES.
12 (c) "EV SUPPLY EQUIPMENT" MEANS:
13 (I) AN ELECTRIC VEHICLE CHARGING SYSTEM AS DEFINED IN
2 14 SECTION 38-12-601 (6)(a) THAT HAS POWER CAPACITY OF AT LEAST 6.
15 KILOWATTS AND HAS THE ABILITY TO CONNECT TO THE INTERNET; OR
16 (II) AN INDUCTIVE RESIDENTIAL CHARGING SYSTEM FOR
17 BATTERY-POWERED ELECTRIC VEHICLES THAT:
18 (A) IS CERTIFIED BY UNDERWRITERS LABORATORIES OR AN
19 EQUIVALENT CERTIFICATION;
20 (B) COMPLIES WITH THE CURRENT VERSION OF ARTICLE 625 OF
21 THE NATIONAL ELECTRICAL CODE, PUBLISHED BY THE NATIONAL FIRE
22 PROTECTION ASSOCIATION, AND OTHER APPLICABLE INDUSTRY
23 STANDARDS;
24 (C) IS ENERGY STAR CERTIFIED; AND
25 (D) HAS THE ABILITY TO CONNECT TO THE INTERNET.
26 (d) "GROUP A, B, E, I, M, OR S-2 OCCUPANCY" MEANS:
2021 27 (I) "GROUP A OCCUPANCY", AS DESCRIBED IN THE
28 INTERNATIONAL BUILDING CODE;
2021 29 (II) "GROUP B OCCUPANCY", AS DESCRIBED IN THE
30 INTERNATIONAL BUILDING CODE;
31 (III) "GROUP E OCCUPANCY", AS DESCRIBED IN THE
32 2021INTERNATIONAL BUILDING CODE;
2021 33 (IV) "GROUP I OCCUPANCY", AS DESCRIBED IN THE
34 INTERNATIONAL BUILDING CODE;
2021 35 (V) "GROUP M OCCUPANCY", AS DESCRIBED IN THE
36 INTERNATIONAL BUILDING CODE; OR
2021 37 (VI) "GROUP S-2 OCCUPANCY", AS DESCRIBED IN THE
38 INTERNATIONAL BUILDING CODE.
39 (e) "HIGH-OCCUPANCY BUILDING PROJECT" MEANS:
40 (I) A MULTIFAMILY BUILDING; OR
41 (II) A LARGE COMMERCIAL BUILDING PROJECT.
42 (f) "LARGE COMMERCIAL BUILDING PROJECT" MEANS:
43 (I) A BUILDING WITH TWENTY-FIVE THOUSAND SQUARE FEET OR
44 MORE OF FLOOR SPACE THAT IS USED OR INTENDED TO BE USED FOR
45 COMMERCIAL PURPOSES; OR
46 (II) A PROJECT TO BUILD FORTY THOUSAND SQUARE FEET OR MORE
47 OF FLOOR SPACE IN MORE THAN ONE BUILDING WITH A TOTAL OF
48 TWENTY-FIVE OR MORE SETS OF LIVING QUARTERS OR COMMERCIAL UNITS
49 IN ALL THE BUILDINGS.
50 (g) "LEVEL 3 CHARGING" MEANS EV SUPPLY EQUIPMENT THAT:
51 (I) USES A MINIMUM OF ONE HUNDRED AMPERES;
52 (II) USES A FOUR HUNDRED EIGHTY VOLT AND THREE-PHASE VOLT
53 CIRCUIT; AND
54 (III) CONVERTS THE ALTERNATING CIRCUIT VOLTAGE INTO DIRECT
55 CURRENT VOLTAGE THAT DIRECTLY CHARGES AN ELECTRIC VEHICLE.
1 (h) "MULTIFAMILY BUILDING" MEANS A RESIDENTIAL BUILDING
2 WITH AT LEAST THREE FAMILY UNITS AND AT LEAST TEN PARKING SPACES.
3 SECTION 3. In Colorado Revised Statutes, 12-115-120, add (11)
4 as follows:
5 12-115-120. Inspection - permit - rules - exemption. (11) THE
6 BOARD SHALL PROMULGATE RULES:
7 (a) REQUIRING COMPLIANCE WITH SECTION 38-47-104 TO BE
8 ISSUED AN INSPECTION PERMIT UNDER THIS SECTION; AND
9 (b) SETTING STANDARDS FOR WAIVING THE REQUIREMENT TO
10 COMPLY WITH SECTION 38-47-104 TO BE ISSUED AN INSPECTION PERMIT
11 UNDER THIS SECTION.".
12
13 Renumber succeeding sections accordingly.
14
15

House Journal, April 19
42 Amendment No. 1, Energy & Environment Report, dated April 14, 2022,
43 and placed in member’s bill file; Report also printed in House Journal,
44 April 18, 2022.
45
46 As amended, ordered engrossed and placed on the Calendar for Third
47 Reading and Final Passage.
48

Senate Journal, April 26
After consideration on the merits, the Committee recommends that HB22-1218 be
amended as follows, and as so amended, be referred to the Committee of the Whole with
favorable recommendation.
Amend reengrossed bill, page 11, line 5, after "DRAFTING FOR" insert "THE
DESIGN OF".

Page 11, strike lines 13 through 20 and substitute "HAVE FIVE PERCENT OF THE
PARKING SPACES USED BY THE OCCUPANTS OF THE BUILDING TO HAVE EV
SUPPLY EQUIPMENT INSTALLED ADJACENT TO A PARKING SPACE; AND".

Page 12, line 7, after "DRAFT," insert "DESIGN,".

Page 15, line 22, after the period add "THIS SUBSECTION (11)(b) DOES NOT
CHANGE THE REQUIREMENT FOR AN ELECTRICAL PERMIT AS REQUIRED IN
SUBSECTION (1) OF THIS SECTION OR THE REQUIREMENT FOR AN ELECTRICAL
INSPECTION AS REQUIRED IN THIS ARTICLE 115.".


Trans- The Committee on Transportation & Energy has had under consideration and has had a
portation & hearing on the following appointments and recommends that the appointments be placed
Energy on the consent calendar and confirmed:

MEMBER OF THE
FRONT RANGE PASSENGER RAIL DISTRICT BOARD

for a term expiring April 1, 2026:

Claire Levy of Boulder, Colorado, to serve as a resident of a city and county through
which commuter rail service was planned as a part of the voter approved RTD Fastracks
Transit Expansion Program but has not been constructed, appointed.


State,
Veterans, &
Military
Affairs

Senate Journal, April 29
HB22-1218 by Representative(s) Valdez A.; also Senator(s) Winter--Concerning resource efficiency
related to constructing a building for occupancy.

Amendment No. 1, Transportation & Energy Committee Amendment.
(Printed in Senate Journal, April 26, page(s) 1002 and placed in members' bill files.)

Amendment No. 2(L.013), by Senator Winter.

Amend reengrossed bill, page 10, strike lines 21 through 23.

Page 15, after line 13, insert:
"SECTION 2. Repeal of relocated provisions in this act. In Colorado
Revised Statutes, repeal 38-35.7-106, 38-35.7-107, and 38-35.7-109.".


Amendment No. 3(L.014), by Senator Winter.

Strike the Transportation and Energy Committee Report and substitute:

"Amend reengrossed bill, page 11, line 5, after "DRAFTING FOR" insert "THE
DESIGN OF".

Page 11, line 14, strike "TEN" and substitute "TWENTY-FIVE".

Page 11, line 15, after "CAPABLE;" add "AND"

Page 11, strike lines 18 through 20.

Page 11, line 24, after "CAPABLE;" add "AND".

Page 11, strike lines 26 and 27 and substitute "THE OCCUPANTS OF THE
BUILDING THAT IS EV READY.".

Page 12, strike lines 1 and 2.

Page 12, line 7, after "DRAFT," insert "DESIGN,".

Page 12, strike lines 13 through 20.

Page 13, strike lines 22 through 27.

Page 14, strike lines 1 through 21.

Reletter succeeding paragraphs accordingly.

Page 15, strike lines 6 through 11.

Reletter succeeding paragraphs accordingly.

Page 15, strike lines 14 through 22.

Renumber succeeding sections accordingly.

As amended, ordered revised and placed on the calendar for third reading and final
passage.



Senate Journal, May 4
HB22-1218 by Representative(s) Valdez A.; also Senator(s) Winter and Priola--Concerning resource
efficiency related to constructing a building for occupancy.

A majority of those elected to the Senate having voted in the affirmative, Senator Winter
was given permission to offer a third reading amendment.

Third Reading Amendment No. 1(L.017), by Senator Winter.

Amend revised bill, page 3, strike lines 10 through 13 and substitute
"photovoltaic solar generation system could provide. The list of businesses shall
be derived from a master list of Colorado solar installers maintained by the
Colorado solar energy industries association, or a successor organization.".

The amendment was passed on the following roll call vote:

YES 34 NO 0 EXCUSED 1 ABSENT 0
Bridges Y Ginal Y Lee Y Simpson Y
Buckner Y Gonzales Y Liston Y Smallwood Y
Coleman Y Hansen Y Lundeen Y Sonnenberg Y
Cooke Y Hinrichsen Y Moreno Y Story Y
Coram Y Hisey Y Pettersen Y Winter Y
Danielson Y Holbert Y Priola Y Woodward Y
Donovan Y Jaquez Y Rankin Y Zenzinger Y
Fields Y Kirkmeyer Y Rodriguez Y President Y
Gardner E Kolker Y Scott Y

A majority of those elected to the Senate having voted in the affirmative, Senator Winter
was given permission to offer a third reading amendment.

Third Reading Amendment No. 2(L.016), by Senator Winter.

Amend revised bill, page 14, before line 1 insert:

"SECTION 3. In Colorado Revised Statutes, 12-115-120, add (11) and
(12) as follows:
12-115-120. Inspection - permit - rules - exemption. (11) THE BOARD
SHALL PROMULGATE RULES:
(a) REQUIRING COMPLIANCE WITH SECTION 38-47-104 TO BE ISSUED AN
INSPECTION PERMIT UNDER THIS SECTION; AND
(b) SETTING STANDARDS FOR WAIVING THE REQUIREMENT TO COMPLY
WITH SECTION 38-47-104 TO BE ISSUED AN INSPECTION PERMIT UNDER THIS
SECTION IF THE WAIVER IS FOR THE RENOVATION OF FIFTY PERCENT OR MORE OF
AN EXISTING HIGH-OCCUPANCY BUILDING PROJECT.
(12) NOTWITHSTANDING SUBSECTION (10) OF THIS SECTION, AN ENTITY
OTHER THAN THE STATE THAT CONDUCTS ELECTRICAL INSPECTIONS MAY WAIVE
THE REQUIREMENT THAT AN INSPECTION PERMIT APPLICANT COMPLIES WITH
SECTION 38-47-104 TO BE ISSUED AN INSPECTION PERMIT UNDER THIS SECTION
IF THE WAIVER IS FOR THE RENOVATION OF FIFTY PERCENT OR MORE OF AN
EXISTING HIGH-OCCUPANCY BUILDING PROJECT.".

Renumber succeeding sections accordingly.

The amendment was passed on the following roll call vote:

YES 34 NO 0 EXCUSED 1 ABSENT 0
Bridges Y Ginal Y Lee Y Simpson Y
Buckner Y Gonzales Y Liston Y Smallwood Y
Coleman Y Hansen Y Lundeen Y Sonnenberg Y
Cooke Y Hinrichsen Y Moreno Y Story Y
Coram Y Hisey Y Pettersen Y Winter Y
Danielson Y Holbert Y Priola Y Woodward Y
Donovan Y Jaquez Y Rankin Y Zenzinger Y
Fields Y Kirkmeyer Y Rodriguez Y President Y
Gardner E Kolker Y Scott Y

The question being "Shall the bill, as amended, pass?", the roll call was taken with the
following result:

YES 20 NO 14 EXCUSED 1 ABSENT 0
Bridges Y Ginal Y Lee Y Simpson N
Buckner Y Gonzales Y Liston N Smallwood N
Coleman Y Hansen Y Lundeen N Sonnenberg N
Cooke N Hinrichsen N Moreno Y Story Y
Coram N Hisey N Pettersen Y Winter Y
Danielson Y Holbert N Priola Y Woodward N
Donovan Y Jaquez Y Rankin N Zenzinger Y
Fields Y Kirkmeyer N Rodriguez Y President Y
Gardner E Kolker Y Scott N